SINIAT LININGS FIRE HAZARD PROPERTIES REPORT
– FAR 4659
Report FAR 4659 lists the Group Number and Average Specific Extinction Area of all Siniat wall and ceiling linings in accordance with AS 5637.1 : 2015.
The BCA (Building Code of Australia) regulates the fire hazard properties of lining materials in Class 2 to 9 buildings according to Specification C1.10. Wall and ceiling linings must have a low enough group number for use in certain areas depending on the Class of building. The group number indicates how quickly wall and ceiling linings spread fire with Group 1 products the slowest and Group 4 the fastest. Wall and ceiling linings in some buildings must also have an Average Specific Extinction Area less than 250 m2/kg.
All Siniat wall and ceiling linings tested had an Average Specific Extinction Area of <250 m2/kg as required by S7C4 of the NCC [2019: C1.10 Clause 4].
Group No. | |
Siniat Mastashield | 1 |
Siniat Spanshield | 1 |
Siniat Watershield | 1 |
Siniat Soundshield | 1 |
Siniat Fireshield | 1 |
Siniat Multishield | 1 |
Siniat Impactshield | 1 |
Siniat Opal | 1 |
Siniat Trurock | 1 |
Siniat Shaftliner | 1 |
Siniat Intershield | 1 |
Siniat Creason & Siniat Createx | 1 |